12
Setting GUD/GCD Manifold Pressure
Only small variations in gas flow should be made when adjusting the gas valve pressure regulator. For propane gas,
the manifold pressure must 9.7 to 10.3” W.C.
WARNING
To prevent death or personal injury due to carbon monoxide, all hoses must be connected
as shown in Figure 12. Failure to connect the hose between the pressure switch and the
burner box could result in excessive generation of carbon monoxide.
BURNER
BOX
VENT
BLOWER
A - CAP OVER ADJUSTMENT SCREW MUST
BE IN PLACE WHEN FURNACE IS
OPERATING.
B - SEE PRESSURE SWITCH DIAGRAM
FOR PRESSURE SWITCH HOSE
CONNECTIONS.
C - HOSE BETWEEN GAS VALVE AND AIR
BOX (TEE TO BE SUPPLIED BY
SERVICER.)
D - TAPPED OPENING IN MANIFOLD (HOSE
BARB TO BE SUPPLIED BY SERVICER.)
TO MEASURE MANIFOLD PRESSURE CON-
NECT MANOMETER BETWEEN C AND D.
MPL
TRIDELTA
TRIDELTA
PRESSURE SWITCH DIAGRAM
PRESSURE
SWITCH
TO
BUR NER
BOX
TO
VENT
BLOWE R
(ALL METAL B ODY)
TO
BURNER
BOX
TO
VENT
BLOWER
(METAL & PLASTIC BODY)
(RO TATED 90 FOR CLARITY)
TO
BURNER
BOX
TO
VENT
BLOWER
GAS VALVE
A
C
D
U-TUBE MANOMETER
10291404
B
Figure 12
GUD, GCD Manifold Pressure Measurement
1. Turn OFF gas to the unit at the manual gas shutoff valve.
2. Connect a calibrate “U” tube manometer (or appropriate gas pressure gauge) between the tapped outlet in the gas
manifold and a tee (field-supplied) in the hose from the burner box to the gas valve.
3. Turn ON gas supply and operate unit. NOTE: Burner box cover must be in place.
4. Remove the cover over the manifold pressure regulator screw.
5. Adjust manifold pressure. Turn adjustment screw out (counterclockwise) to decrease pressure. Turn adjustment
screw in (clockwise) to increase pressure.
6. Reinstall the cover over the manifold pressure regulator adjustment screw in order to check manifold pressure.
Make further adjustments if necessary.
7. Turn OFF gas supply to unit and disconnect manometer.
8. Go to “Unit Operation Check and Labelling” section.