FURNACE SPECIFICATIONS
10 Rev. 1
1. These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane
gas operation.
2. For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace
must not be derated, orifice changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers
method in accordance with the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the
AIR CONDITIONING CONTRACTORS OF AMERICA. The total heat loss calculated should be equal to or less
than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times output.
4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.
MODEL
GUIC045CA30
GUIC045CX30
GUIC045DA30
GUIC045DX30
GUIC070CA30
GUIC070CX30
GUIC070DA30
GUIC070DX30
GUIC070CA40
GUIC070CX40
GUIC070DA40
GUIC070DX40
GUIC090CA30
GUIC090CX30
GUIC090DA30
GUIC090DX30
GUIC090CA50
GUIC090CX50
GUIC090DA50
GUIC090DX50
GUIC115CA40
GUIC115CX40
GUIC115DA40
GUIC115CA50
GUIC115CX50
GUIC115DA50
GUIC115DX50
GUIC140CA50
GUIC140CX50
GUIC140DA50
Btuh Input (US) 46,000 69,000 69,000 92,000 92,000 115,000 115,000 140,000
Output (US) 36,800 55,200 55,200 73,600 73,600 92,000 92,000 110,400
A.F.U.E. 80% 80% 80% 80% 80% 80% 80% 80%
Rated External Static (" w.c.) .10 - .50 .12 - .50 .12 - .50 .15 - .50 .15 - .50 .20 - .50 .20 - .50 .20 - .50
Temperature Rise (°F) 35 - 65 35 - 65 35 - 65 40 - 70 40 - 70 40 - 70 40 - 70 45 - 75
Pressure Switch Trip Point (" w.c.) -0.55 -0.55 -0.55 -0.55 -0.55 -0.55 -0.55 -0.55
Blower Wheel (D" x W") 9 x 8 9 x 8 10 x 6 10 x 8 10 x 8 10 x 7 10 x 9 10 x 9
Blower Horsepower 1/3 1/3 1/2 1/2 1/2 1/2 3/4 3/4
Blower Speeds 44444444
Max CFM @ 0.5 E.S.P. 1200 1290 1450 1380 1980 1590 1985 2050
Power Supply 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1
Minimum Circuit Ampacity (MCA) 8.6 8.5 10.4 8.2 14.6 13.1 13.7 14.6
Maximum Overcurrent Device 15 15 15 15 15 15 15 15
Transformer (VA) 40 40 40 40 40 40 40 40
Heat Anticipator 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
Primary Limit Setting (°F) 230 220 170 170 or *150 170 or *160 170 or *150 190 or *180 135
Auxiliary Limit Setting (°F) 160 160 160 160 160 160 160 160
Rollout Limit Setting (°F) 275 300 300 300 300 350 350 325
Fan Delay On 30 secs. 30 secs. 30 secs. 30 secs. 30 secs. 30 secs. 30 secs. 30 secs.
Off Heating * 90 secs. 90 secs. 90 secs. 90 secs. 90 secs. 90 secs. 90 secs. 90 secs.
Off Cooling 45 secs. 45 secs. 45 secs. 45 secs. 45 secs. 45 secs. 45 secs. 45 secs.
Gas Supply Pressure (Natural/Propane) ("w.c.) 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11
Manifold Pressure (Natural/Propane) ("w.c.) 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10
Orifice Size (Natural/Propane) #43 / #55 #43 / #55 #43 / #55 #43 / #55 #43 / #55 #43 / #55 #43 / #55 #43 / #55
Number of Burners 23344556
Vent Connector Diameter (inches) 44444444
Shipping Weight (lbs.) 140 151 152 169 178 190 194 198
*150 = The GUIC115**40 furnaces can also use primary limit part #10728332 in place of limit part #10728319 but without limit baffle part #11094802.
*180 = The GUIC115**50 furnaces can also use primary limit part #10728334 in place of limit part #10728304 but without limit baffle part #11094802.
* Off Heating - This fan delay timing is adjustable (60, 90, 120 or 180 seconds), 90 seconds as shipped.
*150 = The GUIC090**30 furnaces can also use primary limit part #10728332 in place of limit part #10728319 but without limit baffle part #11094802.
*160 = The GUIC090**50 furnaces can also use primary limit part #10728331 in place of limit part #10728304 but without limit baffle part #11094802.