Amana CKF60 Betriebsanleitung Seite 4

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 12
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 3
4
NOTE: Be careful not to kink or dent refrigerant lines. Kinked
or dented lines will cause poor performance or compressor
damage. Do NOT make final refrigerant line connection until
plugs are removed from refrigerant tubing.
1. The ends of the refrigerant lines must be cut square,
deburred, cleaned, and be round and free from nicks or
dents. Any other condition increases the chance of a
refrigerant leak.
2. “Sweep” the refrigerant line with nitrogen or inert gas
during brazing to prevent the formation of copper-oxide
inside the refrigerant lines. A blockage or failure of the
metering device could result if copper-oxide is flushed
into the metering device.
3. After brazing, quench the joints with water or a wet cloth
to prevent overheating of the service valve.
Co nd
Unit
Tons Suct Liq Su ct Liq Suct Liq
1 1/2 15.9 6.4 19.1 9.5 19.1 9.5
2 19.1 9.5 19.1 9.5 19.1 9.5
2 1/2 19.1 9.5 *19.1 9.5 22.2 12.7
3 19.1 9.5 22.2 9.5 22.2 12.7
3 1/2 19.1 9.5 22.2 9.5 28.6 12.7
4 22.2 9.5 28.6 9.5 28.6 12.7
5 22.2 9.5 28.6 9.5 28.6 12.7
Line Diameter OD (mm)
REFRIGERANT LINE LENGTH (METERS)
0-7.5 7.6-15.1 15.2-22.6
>>
* - 19.1 mm REQUIRED FOR FULL RATINGS
^ - 22.2 mm REQUIRED FOR FULL RATINGS
4. Ensure the filter drier paint finish is intact after brazing. If
the paint of the steel filter drier has been burned or
chipped, repaint or treat with a rust preventative. This is
especially important on suction line filter driers which
are continually wet when the unit is operating.
NOTE: Before brazing, verify indoor piston size by checking
the piston kit chart packaged with indoor unit.
Leak Testing (Nitrogen or Nitrogen-Traced)
Pressure test the system to approximately 100 PSI with dry
nitrogen and use soapy water to locate leaks. If you wish to
use a leak detector, charge the system to 10 psi using the
appropriate refrigerant then use nitrogen to finish charging
the system to working pressure then apply the detector to
suspect areas. If leaks are found, repair them. After repair,
repeat the pressure test. If no leaks exist, proceed to system
evacuation.
System Evacuation
NOTE: Scroll compressors should never be used to evacu-
ate or pump down a heat pump or air conditioning system.
1. Connect the vacuum pump with 250 micron capability to
the service valves.
2. Evacuate the system to 250 microns or less using suction
and liquid service valves. Using both valves is necessary
as some compressors create a mechanical seal separat-
ing the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes.
Typically pressure will rise during this period.
If the pressure rises to 1000 microns or less and
remains steady the system is considered leak-free;
proceed to startup.
If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or non-condensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.
If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as
necessary.
If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as
necessary then repeat evacuation.
System Start Up
When opening valves with retainers, open each valve only
until the top of the stem is 1/8" from the retainer. To avoid loss
of refrigerant, DO NOT apply pressure to the retainer. When
opening valves without a retainer remove service valve cap
and insert a hex wrench into the valve stem and back out the
stem by turning the hex wrench counterclockwise. Open the
valve until it contacts the rolled lip of the valve body. NOTE:
These are not back-seating valves. It is not necessary to
force the stem tightly against the rolled lip. Open the suction
service valve first! If the liquid service valve is opened first, oil
from the compressor may be drawn into the indoor coil TXV,
restricting refrigerant flow and affecting operation of the
system. After the refrigerant charge has bled into the system,
open the liquid service valve. The service valve cap is the
secondary seal for the valves and must be properly tightened
to prevent leaks. Make sure cap is clean and apply refrigerant
oil to threads and sealing surface on inside of cap. Tighten
cap finger-tight and then tighten additional 1/6 of a turn (1
wrench flat), or to the following specification, to properly seat
the sealing surfaces.
Seitenansicht 3
1 2 3 4 5 6 7 8 9 10 11 12

Kommentare zu diesen Handbüchern

Keine Kommentare